Guangzhou Hiseer Air Conditioning Co.,Ltd

Begin your green life with HISEER high efficiency heat pumps, reduce your carbon emissions, enhance your comfort and improve lives.

Sales & Support
Email:export@chinaheatpump.com
Request A Quote
Select Language
HomeProductsAir Cooled Heat Pumps

Home low cost saving water air cooling heat exchanger

Certifications
China  good quality  Chinese Heat Pump on sales China  good quality  Chinese Heat Pump on sales
My experience is that your heatpumps is getting better and better.It seems you choose quality before low price and that is good. I am satisifed wit

—— Henning from Norway

I'm Online Chat Now
Call me!
点击这里给我发消息
86-20-61168935
export@chinaheatpump.com

Home low cost saving water air cooling heat exchanger

Large Image : Home low cost saving water air cooling heat exchanger

Product Details:

Place of Origin:Guangzhou, China
Brand Name:HISEER
Certification:CE EN14511
Model Number:AW12/B-QNNNS

Payment & Shipping Terms:

Minimum Order Quantity:2 pieces
Packaging Details:plywood
Delivery Time:10-15 days after TT payment
Payment Terms:TT payment
Supply Ability:100 pieces each day
Detailed Product Description

Home low cost saving  water air cooling heat exchanger

AW12/B-QNNNS, stainless steel high efficiency air to water heat pump. ASHPs supply more energy than they consume. By extracting heat from the surrounding air, the heat energy released can be up to 4 times the energy required to power the equipment.

HISEER AW12/B-QNNNS, heating & cooling unit, 220-240V/1/50Hz, 443 stainless steel cabinet, R410a refrigeration, designed and tested by EN14511, approved by TUV china branch, adopts the following world famous parts:
* SWEP or GEA plate type heat exchanger
* Siemens controller
* Daikin scroll compressor
* Schneider A/C contactor
* Emersion thermal expansion valve
* Emersion dry filter
*Soft start is standard part

Air-source heat pumps, often used in moderate climates, use the difference between outdoor air temperatures and indoor air temperatures to cool and heat your home, at the same time to supply domestic hot water.

How does a air source heat pump work?
An air source heat pump is made up of three main components - an evaporator coil, a compressor, and a heat exchanger.
The evaporator coil is fitted to the outside of an external wall. It absorbs heat from the outside air. The compressor pushes the refrigerant gas through the system compressing it until it is at the desired temperature (typically up to 35-40 degrees Celsius). The hot refrigerant then passes through the heat exchanger where the heat from the refrigerant is transferred to water or air.

The operation of a heat pump can be reversed and used to cool down the air in a building by radiating it outside - behaving in exactly the same way as a refrigerator.

Coefficient of performance
Heat pumps are measured by their coefficient of performance (COP). The COP for air source heat pumps is very similar to that for ground source heat pumps at approximately 2-3. With a COP for instance of 3, 3 units of heat are produced for every 1 unit of electricity consumed. (The two free units of heating were extracted from the outside air). Even with ambient air temperatures of -10 to -15 degrees Celsius, an air source heat pump can extract useful heat (i.e. > 1 unit of heat generated per unit of electricity consumed).

 

AW12/B-QNNNS technical data

AIR TO WATER HEAT PUMP

AW12/B-QNNNS

Heat output/Power consumption at 7/35℃

kW

13.0/3.6

Heat output/Power consumption at 7/45℃

kW

12.5/4.2

Heat output/Power consumption at 7/55℃

kW

12.2/5.3

Heat output/Power consumption at 2/35℃

kW

11.1/3.5

Heat output/Power consumption at 2/45℃

kW

10.8/4.2

Heat output/Power consumption at -7/35℃

kW

8.0/3.5

Heat output/Power consumption at -7/45℃

kW

7.9/4.2

Cool output/Power consumption at 35/7℃

KW

11.5/4.3

Starting current 

A

36

Soft-start relay

 

Included as standard

Power

 

220-240V/1PH/50Hz

Compressor

 

DAIKIN Scroll

Condenser

 

Brazed plate heat exchanger

Nominal flow heating medium

l/s

0.62

Internal pressure drop at nominal flow

kPa

20

Air flow

m3/h

5000

Nominal output fan

W

300

Max outgoing heating medium temperature

55℃

Dimensions(HxWxD)

mm

1075x1105x505

Pipe connector

 

DN25

Weight

kg

175

The above data is tested by EN14511

 

Guangzhou Hiseer Air Conditioning Co.,Ltd

Tel:86-20-61168935

Fax:86-20-61168929

Contact Person: Ms. Shelly Yan

Send your inquiry directly to us

(0 / 3000)
Copyright © 2011 - 2012 chineseheatpump.com. All rights reserved.
English
French
German
Italian
Russian
Spanish
Portuguese
Dutch
Greek
Japanese
Korean